IAEI Questions

 

Please Note: All answers given for the questions below are for discussion purposes ONLY, and are not to be taken as formal interpretations by the Minnesota Chapter IAEI, the Minnesota State Board of Electricity or the employers of the Code Panel members.

The Minnesota Chapter would like to thank the Code Panel members, Michael Buck, Tom Lichtenstein, Mark Earley and Mike Forister for taking time from their busy schedules to participate in this panel, plus the time they have used to research and answer these questions.

 

1. Is GFCI protection required for a 125-volt, single-phase, 15 amp receptacle, installed outdoors at a place of business that is normally not open to the general public?  The company has multiple employees, but there are no gates or fences to preventing access to the building.

 

In the 2002 Code, GFCI protection was required for the exterior receptacle outlets installed in other than dwelling units for rooftop receptacles.

In the 2005 Code 422.51, Cord-and-Plug-Connected Vending Machines was added.  The new section requires cord-and-plug-connected vending machines manufactured or re-manufactured on or after January 1, 2005 to have a ground-fault circuit-interrupter as an integral part of the plug and or cord assembly.  Cord-and-plug-connected vending machines not incorporating integral GCFI protection shall be connected to a GFCI protected outlet.

To accomplish this 210.8(B) (4) and (5) added the GFCI requirement for receptacles installed outdoors.  Specifically 210.8(B) (4) applies to outdoor locations in public spaces and defines a “public space” as a space that is for use by or accessible to the public.  Since the place of business in the question is not guarded by locked doors or fences, GFCI protection would be required.  

 

 

2. Are energy management and communication cables (CL 2 cable) required to be plenum rated when installed inside a listed, nonmetallic, plenum-rated signaling raceway in the space over a return-air (plenum) ceiling?

 

Yes, 725.61(A) only permits type CL 2P and CL 3P cables in these raceways.

 

3. Can THHN grounding electrode conductor be installed in a listed nonmetallic plenum signaling raceway installed in the space over a hung ceiling used for environmental air handling purposes? Can the same conductor be installed in EMT?

 

Article 760.3(B)((Fire Alarms)) refers to the requirements of Article 300.22 for installations in Ducts, Plenums, and other Air Handling Spaces. Article 300.22(C) specifies the acceptable wiring methods in the cavity above the dropped ceiling where the cavity is used for environmental air. The wiring methods do not include listed nonmetallic plenum signaling raceway. EMT is an acceptable wiring method.

Listed nonmetallic plenum communication raceway is allowed in plenums for communication circuits according to Article 800.154(A) using only Type CMP cable.

 

 

4.Is GFCI protection required for a 125-volt 20 amp receptacle that is installed 15 feet above the sidewalk under the canopy (for holiday lights) at a retail store?

 

No.  Section 210.8(B)(4) requires a GFCI for other than dwelling units outside in public spaces where accessible to the public.  Because this receptacle is 15 feet in the air and would need a ladder to reach it, it would not comply with the definition of accessible in Article 100 because of elevation.

 

 

5.Would a 20 amp 125-volt receptacle used to provide power for a pump-motor that pumps water out of ponds, lakes or rivers, need to be GFCI protected when used to provide water to a sprinkler system outdoors at a office building?

Note: The receptacle is not accessible to the public, but is within the electrical datum plain of the pond, lake or river. Could the pump be direct-wired (without the receptacle)?

 

In the 2002 Code, GFCI protection was required for the exterior receptacle outlets installed in other than dwelling units for rooftop receptacles.

In the 2005 Code 422.51, Cord-and-Plug-Connected Vending Machines was added.  The new section requires cord-and-plug-connected vending machines manufactured or re-manufactured on or after January 1, 2005 to have a ground-fault circuit-interrupter as an integral part of the plug and or cord assembly.  Cord-and-plug-connected vending machines not incorporating integral GCFI protection shall be connected to a GFCI protected outlet. 

To accomplish this 210.8(B) (4) and (5) added the GFCI requirement for receptacles installed outdoors.  Specifically 210.8(B) (4) applies to outdoor locations in public spaces and defines a “public space” as a space that is for use by or accessible to the public.  Since the place of business in the question is not guarded by locked doors or fences, GFCI protection would be required.  

 

 

 

6.Would Section 700.27 require a 2000 amp GFPE service at an office building to be selectively coordinated with the 1200 amp feeder that subsequently feeds a 200 amp feeder? 

Note:  The two hundred-amp feeder runs to a transfer switch (also supplied by an emergency generator) that feeds a main lug 200 amp emergency lighting panelboard with 20 amp lighting circuits used to supply egress lights. The two hundred-amp breaker in the generator is selectively coordinated with the 20 amp emergency lighting circuits.

 

The intent of this section is to isolate the fault within the emergency system so that the entire system is not affected.  Coordination within the emergency system is what is intended here.  This section only applies to the emergency system, not to the service.

 

 

7.How much detail is required to comply with the requirement in 408.4 to fill out the panel directory? Could each of the two-kitchen appliance circuits be identified simply as “appliance”? Could each of the two bedroom AFCI breakers be simply marked “bedrooms 1 & 2” “bedrooms 3 & 4”?

 

The requirement is that each circuit shall be identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all others. It may not be clear to anyone which bedroom is 1, 2, 3, or 4. It should be made clear where the rooms are, for instance: Northwest bedroom, southwest bedroom, etc. Kitchen appliance circuit may be specific enough.

 

8.When fixture whips containing a white and a black conductor are installed in a building with two nominal voltage systems and used to supply both 120 and 277 volt luminaires, is re-identification required for the black conductor when used on an ungrounded circuit that is other than a black?  If so, to what extent? Is re-identification required for the white conductor when used on a 277 volt lighting circuit?

 

Note:  The current identification for conductors in the building is 120/208  A phase is black, B phase is red and C phase is blue and grounded conductor is white. The 277/480 is A phase is brown, B phase is orange and C phase is yellow and grounded conductor is gray.

 

Yes and Yes sometimes.  For the black conductor, Section 210.5(C) requires where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by system. The means of identification shall be permitted to be by separate color coding, marking tape, tagging, or other approved means and shall be permanently posted at each branch-circuit panelboard or similar branch-circuit distribution equipment.

For the White Conductor, 200.6(D) requires that the grounded conductor of different systems be identified where the ungrounded conductors of both system are present in the same raceway, enclosure, cable or equipment.  And that the identification means to differentiate between systems be permanently marked at each branch circuit panelboard.

 

 

9.Is AFCI protection required for a 125-volt 15 amp outlet in a guest suite bedroom? Would it make a difference if it had a kitchen in the suite?

 

210.12(B) requires AFCI protection in dwelling unit bedrooms.  A kitchen in a hotel room can make it a dwelling unit.  See article 100 definition of a dwelling unit.  See also Section 210.18.

 

10.Where is AFCI protection required in an efficiency apartment?

 

Provided the “efficiency apartment” meets the definition of a “dwelling unit”, AFCI protection is required for the bedroom according to Article 210.12. If the living area and the bedroom are one and the same, AFCI protection would be required.

 

11.Is NM cable considered secured or supported when installed behind a 1 5/8 inch deep narrow strip of Styrofoam?

Note: The installation practice was to remove a 2 inch deep narrow strip of Styrofoam from a pored concrete wall, the NM cable is then installed and the Styrofoam is trimmed from 2 inches to 1 5/8 inches deep and reinstalled and friction held in place until wall covering is installed.

Would it make a difference if I were to discard the 2- inch strip of Styrofoam and re-foam the NM cable so it is a minimum of 1 ¼ inch back from the face of the Styrofoam?

 

There are three basic Code requirements to be met.  The cable must be protected from physical damage, supported, and secured to the outlet box.

300.4(E) This section relates to protection from physical damage and allows the cable to be installed in shallow grooves without additional protection provided it is maintained at least 1¼ inches back from the face of the groove.  Care must be taken to ensure the cable remains at least 1¼ inches back.

314.17(B) & (C) require all permitted wiring methods to be secured to the (outlet) box.  There is a limited exception for single gang, nonmetallic boxes.

334.30 requires the cable to be secured and supported using an approved means at intervals not exceeding 4½ feet and within 12 inches of each outlet box.  Approved is acceptable to the authority having jurisdiction.  I would accept the minimal support provided by the Styrofoam (raceway) in addition to the securing the cable to the outlet box.

The use of expanding foam is only appropriate where the foam will not have a deteriorating effect on the cable.  This would permit some discretion in allowing the foam to replace the strip of insulation that was removed.  Personally I would not accept this type of installation where I could not see the cable at the rough in inspection.

 

 

12.What minimum size conductors with a rating of THHN/THWN are required to a panelboard with a 400 amp main breaker?

Note: The panelboard is fed from a transformer with a secondary voltage of 120/208 three phase wye, with secondary conductors 20 feet long. The primary is 480 volts three phase protected at 200 amps with 3/0 wire.

 

240.21(C) can’t round up overcurrent protection for transformer secondary conductors.  Therefore, for this application, the minimum conductor size permitted is 600 kcmil

 

 

13.Must the supply water piping to a hydromassage bathtub be bonded when there is no lug on the motor and the pump motor is double insulated? Must the supply water piping be bonded when a hydromassage bathtub has a lug on the motor and the pump motor is supplied wired with a three-conductor cord? If bonding is required, exactly what and how must it be tied together? \What bonding is required if the supply is plastic? 

Note: The tubs re-circulating system is plastic piping in all the above scenarios.

 

NEC Section 680.74 requires that metal piping systems and all grounded metal parts in contact with the circulating water shall be bonded together with a min no. 8AWG. Copper insulated covered or bare.  If the water supply is plastic, there is nothing to bond to, if the pump is Double Insulated there is no grounded parts in contact with the water and no bonding is required.

 

14.If I construct my own equipotential bonding grid with a # 8 bare solid copper conductor around a swimming pool using a one foot on center checker board pattern, the #8 conductor crosses over itself approximately 750 times, do I need to connect theses points of crossing together and if so, do they have to all be connected using a listed means (split bolt connectors approved for direct burial)?

 

Yes, Article 680.26(C)(3) requires the grid to be bonded at all points of crossing. The connections shall be made according to Article 250.8, which requires exothermic welding, listed pressure connectors, listed clamps or other listed means.

 

15.What minimum size grounded conductor (neutral) is required for a 11 ampere calculated load on the grounded conductor of a 50 amp feeder wired with # 8 ungrounded conductors,  and a #10 equipment grounding conductor all in PVC?

 

There are three basic Code requirements to be met.  The cable must be protected from physical damage, supported, and secured to the outlet box.

300.4(E) This section relates to protection from physical damage and allows the cable to be installed in shallow grooves without additional protection provided it is maintained at least 1¼ inches back from the face of the groove.  Care must be taken to ensure the cable remains at least 1¼ inches back.

314.17(B) & (C) require all permitted wiring methods to be secured to the (outlet) box.  There is a limited exception for single gang, nonmetallic boxes.

334.30 requires the cable to be secured and supported using an approved means at intervals not exceeding 4½ feet and within 12 inches of each outlet box.  Approved is acceptable to the authority having jurisdiction.  I would accept the minimal support provided by the Styrofoam (raceway) in addition to the securing the cable to the outlet box.  

The use of expanding foam is only appropriate where the foam will not have a deteriorating effect on the cable.  This would permit some discretion in allowing the foam to replace the strip of insulation that was removed.  Personally I would not accept  this type of installation where I could not see the cable at the rough in inspection.

 

 

16.How do you size a common grounding electrode conductor run to two 30 KVA transformers with derived conductors of # 1 on the secondary feeding 125 amp main breaker panelboards?

 

No. 6 Copper or No. 4 Alumnium for the tap conductors.

 

250.30(A)(4)

 

(4) Grounding Electrode Conductor, Multiple Separately Derived Systems. Where more than one separately derived system is installed, it shall be permissible to connect a tap from each separately derived system to a common grounding electrode conductor. Each tap conductor shall connect the grounded conductor of the separately derived system to the common grounding electrode conductor. The grounding electrode conductors and taps shall comply with 250.30(A)(4)(a) through (A)(4)(c).

 

(a)        Common Grounding Electrode Conductor Size. The common grounding electrode conductor shall not be smaller than 3/0 AWG copper or 250 kcmil aluminum.

(b)        Tap Conductor Size. Each tap conductor shall be sized in accordance with 250.66 based on the derived phase conductors of the separately derived system it serves.            

 

17.Can I use three single pole breakers to feed permanently connected free standing type office partitions with three #12 ungrounded conductors, a #12 equipment grounding conductor and a #10 common neutral all in liquid-tight flexible metal conduit?

 

No, Section 605.6 requires that multiwire circuits feeding office panels be provided with a means to simultaneously disconnect all ungrounded conductors at the panelboard where the branch circuit originated.  You either have to use a 3 phase breaker or handle tie appropriately rated single pole breakers.

 

18. Does Section 210.8(A) (7) apply to receptacles in dedicated spaces, such as the laundry receptacle if it’s behind the clothes washer or dryer?

 

Yes, all 125 volt, 15 or 20 amp receptacles installed within 6’ of the sink must be protected by a GFCI. There is no exception to allow dedicated spaces, non-readily accessible, etc.

 

 

19.Does a metal cut-in box installed in a ceiling for the installation of a smoke detector have to be grounded when fed from a two-wire, ungrounded system in an existing dwelling?

 

Maybe yes, but probably not.

As a point of clarification to the question, the premise wiring system is grounded and the branch circuit wiring method is Type NM cable without an equipment grounding conductor.

 In general, Article 250.86 requires metal enclosures and raceways for other than service conductors to be grounded.  Exception No.1 exempts metal enclosures and raceways for conductors added to existing installations of open wire, knob and tube wiring, and nonmetallic-sheathed cable from the previously stated grounding requirements where the enclosures or wiring methods comply with the (1) through (4) as follows:

 

(1)          Do not provide an equipment ground

(2)          Are in runs of less than 25 feet

(3)          Are free from probable contact with ground, grounded metal, metal lath, or other conductive materials

(4)          Are guarded against contact by persons

 

The nonmetallic smoke detector should adequately guard the metal box from contact by persons and as stated, the branch circuit wiring method does not provide an equipment ground.  If the metal box does not contact grounded metal, metal lath or other conductive material and the circuit extension is less than 25 feet, the metal box would not have to be grounded.

It should be pointed out that smoke detectors shall be provided with power from a central source and smoke detectors shall be interconnected in such a manner that all smoke detectors will sound an alarm when one smoke alarm goes into alarm.

In addition, when interior alterations, repairs, or additions requiring inspections occur, or one or more sleeping rooms are added or created in existing dwellings, the dwelling shall be provided with smoke detectors as required for new construction.

Given these requirements, the length of the run will likely exceed 25 feet and not meet the criteria of the exception.  The Code requirements are the same applying either the 2002 or 2005 NEC.

 

 

20.When replacing metal luminaires in existing structures that do not have equipment grounding means in the box, the luminaires are not accessible from grade or grounded surfaces, what if any additional requirements apply?

 

Per 410.18(B), exc. 2, the circuit must be protected by GFCI.

 

21. If I am wiring a townhome that will have a stackable 240-volt washer/dryer installed, will I still have to install a 20-ampere, 125-volt laundry receptacle? The stackable unit will not use the 125-volt circuit, and it’s just a waste of money.

 

Yes, Article 210.52(F) requires at least one receptacle outlet for the laundry. A stackable washer could be replaced with a 120 volt appliance.

 

22. What exactly is a “vending machine” as described in Section 422.51? Is it food vending only, or can it be other types of similar machines?

 

It is not food machines only, it is any kind of vending machine.  Presently, the standards for these types of machines have not adopted requirements for the GFCI in the cord yet.  So GFCI receptacles for cord-connected vending machines are necessary to comply with this requirement.

 

23. If I install a 125-volt electric baseboard heater on a 20-amp circuit in a bedroom, does this circuit need to be AFCI-protected?

 

Yes.

As a point of clarification, the nominal voltage of the NEC is 120 volts, and Code requirements are not waived if the actual voltage of the circuit varies by a few volts.

Article 210.12 requires arc-fault circuit interrupter protection for all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets installed in dwelling unit bedrooms. 

The NEC defines an outlet as a point on the wiring system at which current is taken to supply utilization equipment and utilization equipment as equipment that utilizes electric energy for electronic, electromechanical, chemical, heating, lighting, or similar purpose.  There are no exceptions that apply.  The requirements were the same in the 2002 NEC.

 

24. Why doesn’t my brand-new, expensive AFCI tester always trip AFCI breakers? If it doesn’t trip, is the breaker faulty?

 

AFCI indicators operate by producing a waveform similar to an arc fault. However, because they cannot produce an actual arc fault, an AFCI indicator may not trip every available AFCI.

Therefore, if an AFCI indicator plugged into a receptacle protected by an AFCI does not trip the AFCI, it does not mean that the AFCI protecting the circuit is defective and needs to be replaced. When this situation occurs, you should push the "Test" button provided as an integral part of the AFCI itself. If the integral test button does not trip the AFCI circuit breaker, it should be replaced.

To notify users of this product limitation, Underwriters Laboratories Inc. requires AFCI indicators to be marked or be provided with instruction manuals that state the following or equivalent:

CAUTION: AFCIs recognize characteristics unique to arcing, and AFCI indicators produce characteristics that mimic some forms of arcing. Because of this the indicator may give a false indication that the AFCI is not functioning properly. If this occurs, recheck the operation of the AFCI using the test and reset buttons. The AFCI button test function will demonstrate proper operation.

 

25. A feeder tap consisting of 500KCMIL copper conductors is connected to a panelboard with a 400 ampere main breaker. Is this a legal installation? 

 

No, you are not allowed to round up to the next overcurrent device according to Article 240.21(B). 500 KCMIL copper conductors are rated 380 amps for 75-degree conductors. The maximum overcurrent device would be 350 amps.

 

26. If I have both a water pipe grounding electrode and a concrete-encased reinforcing rod electrode in the building footings, do I still need to drive a ground rod?

 

 250.53(D)(2)-Supplement water pipe electrode per (A)(2) to (A)(7)

The concrete encased electrode satisfies this requirement.

 

27. Can I run branch circuits overhead between trees for Christmas lights?

 

Yes, as of next Christmas.

In the 2002 NEC, 527.4(J) prohibited the use of vegetation such as trees for the support of overhead spans of branch circuits and feeders.

In the 2005 NEC, Article 527. Temporary Installations, was relocated to Article 590 and renumbered.  An exception was added to 590.4(J) to allow the branch circuits supplying holiday lighting to be supported by trees where the conductors or cables are arranged with proper strain relief devices, tension take-up devices, or other approved means to avoid damage from the movement of the trees.  Temporary electrical power and lighting installations for holiday decorative lighting shall be permitted for a period not exceeding 90 days. 

It should be noted that the exception that allows branch circuit conductors to be supported by trees does not apply to temporary installations for construction, remodeling, maintenance, or similar activities

 

28. Is it required to derate conductors in raceways exposed to direct sunlight?    

 

310.10 Yes if operating temperature is exceeded.  See also 310.10, FPN No. 2.

 

29. In the past, any splices in the grounding electrode conductor(s) had to be done by some type of irreversible splice. If you use the busbar connection point now allowed by Section 250.64(C), do these conductors have to be permanently attached to the busbar, or is bolting connectors acceptable? If bolted are acceptable, then can the connectors themselves be of the “set screw” type, or must they be compression type?

 

This is not considered a splice. Article 250.64(C)(3) allows the use of a busbar to connect bonding jumpers and grounding electrode conductors. It allows the use of listed connectors or exothermic welding. Either listed setscrew type or compression connectors would suffice.

 

 

30. In Section 210.18, does a microwave mounted above a countertop with a cord-and-plug connection qualify as “...permanent provisions for cooking”?

 

No, Extended-stay hotels and motels are often equipped with permanent provisions for cooking and countertop areas such as a cook top range mounted in the counter. A portable microwave oven is not considered to be a permanently installed cooking appliance.

 

31. In an efficiency apartment, which is one room with the bed, kitchen area and living area in it, which receptacles must be on the Small Appliance Branch Circuits? Which receptacles must be AFCI-protected?

 

If an area within a building or structure meets the definition of a dwelling it must be wired in accordance with the requirements for a dwelling including the required branch circuits, minimum number and placement of receptacle outlets, required lighting outlets and switching locations, GFCI, and AFCI protection. 

A single, 15-ampere, general lighting circuit can serve an area up 600 square feet.  That is an area equal to 20’ by 30’.  One such circuit with an arc-fault circuit interrupter protection would likely be adequate. 

Receptacle outlets that could be reasonably expected to serve the kitchen and dining area would be required to be supplied by two small-appliance branch circuits.  GFCI protection would be required for receptacles installed to serve countertop surfaces.

As an inspector, I would not require AFCI protection for the small-appliance branch circuits for the same reason I would not require, or permit the receptacles adjacent to the bed to be supplied by a 20-ampere, small-appliance branch circuit. 

 

 

32. What are the exit requirements for a room containing a 2,000-ampere switchboard that is 5’ high and 3’ wide? If a door was on the wall opposite the switchboard, and you had to go partially around a column to get to the door, would that qualify as an “unobstructed exit”?

 

110.26(C)(2)  Exit requirement is now based on rating of equipment rather than its physical size.  Hard to say.  I wouldn’t consider it unobstructed.  Therefore, I would not consider a single exit to be adequate.

 

33. The local inspector keeps getting complaints that the refrigerators being used by vendors at the County Fair keep tripping the GFCI-protected receptacles. Is it a requirement that these refrigerators be on a ground-fault? Don’t they keep “nuisance tripping” the GFCI?

 

Yes, they are required to be GFCI protected by Section 210.8(B)(2) or (4) depending on the set up at the fair.  If the GFCI’s are tripping, they are not nuisance tripping, they are tripping for a reason, there is excessive leakage current coming from the refrigerators meaning there is some type of fault in the equipment.  The GFCI is doing exactly what it is intended to do.

 

 

34. The local inspector “red-tagged” the temporary wiring for a new store of type III construction, because he said Romex wasn’t allowed to be run in the open according to Section 334.10(3). Is he correct?

 

Article 590.4(C) clarifies that NM cable may be used for temporary wiring in any dwelling, building or structure without any height limitation or limitation by building construction type and without concealment within walls, floor, or ceilings.

 

35. A permanent generator is installed on the ground outside a building. The generator feeds a computer room and the air conditioning equipment for the building. If the generator is installed inside a locking enclosure, does there have to be a disconnecting means on the exterior of the building for the feeder?

 

Loads supplied by optional standby systems are loads that if lost can cause physical discomfort, serious interruption of industrial processes, damage to process equipment, or disruption of business.  The loads listed in the question seem to fit these requirements. 

A generator set typically has an integral circuit breaker that  provides overcurrent protection for the generator as well as providing overcurrent protection for properly sized conductors serving the load connected to the generator.    

Section 702.11 was added in the 2005 Code which allows a readily accessible disconnecting means on, or part of an outdoor generator set to serve as the disconnecting means required by 225.31 when installed within sight of the building or structure supplied.  To be considered within sight the equipment must be visible and not more than 50 feet.

Is the generator set considered readily accessible when installed within a locked enclosure?  Ready access is not considered to be denied by a locked door or enclosure.  Equipment would not be considered readily accessible if a snow blower, snow shovel, or ice pick were required to get to the disconnecting means.

Ready access in not denied by a lock when authorized persons with keys are readily at hand.  An additional disconnecting means would not be required if the generator was otherwise readily accessible.

 

 

36. A new home has a large shelf for a television set mounted near the ceiling over the hydromassage bathtub. There is no shower on this tub. Is it permissible to have a receptacle by the shelf for the TV? Must it be GFCI-protected? If the shelf is metal, must it be bonded to the bathtub?

 

406.8(B)(1)

406.8(C)-Receptacle not permitted in that space

210.8(A)(1)requires bathroom receptacles to be GFCI protected.-But not permitted in that space.

680.74-Bonding to bathtub not required.

 

 

37. In an existing multi-tenant building with a 3,000-ampere 277/480-volt service, there is a proposal for a local health-care provider to put in a “day-surgery” center. This center would have some of the patients put under general anesthetic for an operation. The main service disconnect has GFPE. If this tenant is allowed to go into the building, does this mean that the feeder to each tenant will now have to be retrofitted with an additional level of GFPE per Section 517.17?

 

Yes, this would be a requirement according to Article 517.17(B).

 

38. Does the NEC have a required use of type “CI” (Circuit integrity) cable, or does it just recognize it?   

 

The NEC does not require Circuit Integrity or CI cable, however, it is permitted to ensure critical circuit survivability for continued circuit operation for a specified time under fire conditions in applications as in Section 725.61(H) and 725.82(F) and in Article 760 for fire alarm circuits and in NFPA 72.     

 

39. Where is the ground detector mentioned in Section 250.21 supposed to be located? At the source? At a normally-occupied location?

 

The code does not specify a location.  It is intended to be located where it can be readily seen.

 

40. Is it required to have a “bubble-style” “in-use” cover on a receptacle in an indoor car wash?

 

Yes, Section 406.8(B)(1) dropped the term outdoors from the requirement in the 2005 NEC and requires 15 and 20 A, 125 and 250V receptacles installed in wet locations be provided with bubble covers regardless of indoors or out.

 

41. What types of raceways are acceptable for the underground run from a gas pump on the island at a service station to the interior of the building?

 

Article 514.8 specifies that the underground wiring shall be installed in threaded rigid metal conduit or threaded steel intermediate metal conduit. Exception 2 allows rigid nonmetallic conduit with at least 2 feet of cover. The last two feet from emergence must be threaded rigid metal conduit or threaded steel intermediate metal conduit.

 

 

42. Where does the bonding conductor for a swimming pool have to terminate? In a subpanel? Or all the way back to the service equipment?

 

The intent of the bonding requirements is to establish an equipotential plane to limit the voltage between all non-current-carrying parts of electrical and nonelectrical equipment in the pool area.  A Fine Print Note to 680.26 explains that the only function of the 8 AWG or larger conductor is equipotential bonding to eliminate the voltage gradient in the pool area. 

Where metal parts of electrical equipment are bonded, it has the effect of connecting the equipotential plane to the premise wiring system equipment grounding conductor but the 8 AWG or larger solid copper bonding conductor is not required to be extended or attached to any remote panelboard, service equipment, or any electrode.

 

 

43. Can a cable tray used for service conductors contain other conductors such as feeders?

 

230.44-Cable tray is not permitted unless there is a solid fixed barrier of material (compatible with the cable tray) to separate the service conductors from the other conductors.

 

44. Has any manufacturer come out with the thinner, stronger nail plate that is now allowed in Section 300.4(A)(1) Ex.2? Is there a UL standard for such a product?

 

Not yet, no manufacturer has submitted a thinner plate for Listing.  UL does have Listed plates under the category Conduit and Cable Hardware, (DWMU) located on page 21 in the 2004 White Book.  UL 2239 is the Standard for Conduit and Cable Hardware, presently there are no requirements in the standard for plates less than 0.0625 in. thick.  If a manufacturer would submit for a Listing we would establish Listing criteria to evaluate the thinner plates.

 

 

45. Is a switch with an internal neon pilot light still considered a “Device” under the definition in Article 100, even though it does utilize a small amount of power?

 

Here is a proposal I am submitting for the 2008 Code.   The definition of a device is a unit of an electrical system that is primarily intended to carry or control utilize electric energy.  A device may utilize incidental energy to facilitate its operation.

By definition, a controller is a device or group of devices that serves to govern, in some predetermined manner, the electric power delivered to the apparatus to which it is connected.  Many types of devices and controllers such as lighting dimmers, magnetic starters, variable frequency drives, and programmable controllers consumer electrical power to facilitate their operation as well as generate incidental heat losses due voltage drop across semiconductor junctions.

Simply adding the sentence “A device may utilize incidental energy to facilitate its operation” to the current definition clarifies this issue.

 

 

46. In a restaurant, there is cooking in “kitchen” area, plus they have a salad bar with some 120-volt heating appliances plugged in. There is also a “drink bar” with a soda pop dispenser powered at 120-volts. Where is the “kitchen” area for purposes of enforcing 210.8(B)(2)? Would it include the salad bar and drink dispenser?

 

According to Article 210.8(B)(2) a kitchen is an area with a sink and permanent facilities for food preparation and cooking. A salad bar and the soda pop dispenser would probably not meet the definition. This would be a call shot of the AHJ at to where the “kitchen” ends.

 

 

47. A 120-volt, 20-ampere receptacle is installed behind a very large, heavy freezer in a restaurant kitchen. Does this receptacle need to be GFCI-protected?

 

Yes.

Section 210.8(B)(2) was new in the 2002 Code and required all 15- and 20-ampere, 125 volt receptacles in non-dwelling-type kitchens to be GFCI protected.  This requirement applies to all 15- and 20-ampere, 125-volt kitchen receptacles, whether or not the receptacle serves countertop areas.  However, what actually constituted a kitchen was not clear.

In the 2005 Code, a definition of a commercial and institutional kitchen was added to 210.8(B)(2).  A kitchen is an area with a sink and permanent facilities for food preparation and cooking.

 

Good design practices would provide the GFCI protection in the branch circuit panelboard rather than at the receptacle.

 

48. Assuming that a furnace and an air conditioner have exactly the same circuit requirements, can they both be on the same circuit?

 

Yes.  New Section 422.12 Ex2 now allows this as long as the supply circuit is adequate for both loads. These two loads would be considered noncoincident and should never operate simultaneously.

 

49. A luminaire is listed for use in a Class 1, Zone 0 location. Can this luminaire be used in a Class 1, Zone 2 location instead?

 

Yes, Section 505.9(B)(1) permits Equipment that is listed for a Zone 0 location shall be permitted in a Zone 1 or Zone 2 location of the same gas or vapor, provided that it is installed in accordance with the requirements for the marked type of protection.

 

50. If an isolated ground receptacle is used in a health-care facility, does the isolated ground conductor count as one of the two redundant ground paths for the receptacle?

 

No, Article 517.13(A) requires all branch circuits serving patient care areas be provided with a ground path for fault current by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system or metallic cable armor, or sheath assembly shall itself qualify as an equipment ground return path in accordance with 250.118.

Article 517.13(B) requires an insulated equipment-grounding conductor to ground all fixed electric equipment likely to become energized that are subject to personal contact. This would include boxes. So, these two requirements must be met in addition to the isolated ground.

Article 517.16 allows an isolated ground for receptacles.